Deutz AAD-032 Industrial Generator 32 kVa
Generating set with manual panel.
RPM: 1500
VOLTAGE-HZ: 400/230 50 Hz
PRP: 31 kVA 24.8 kW
LTP: 32 kVA 25.6 kW
ENGINE: F4L2011
ALTERNATOR: LEROY-SOMER
The powers are for reference environmental conditions: 100 kPa barometric pressure, 25º C and 30% relative humidity.
They are defined according to ISO 8528 and ISO 3046. PrimePower (PRP) “Primary Service”: It is applicable for generating sets that function as the main source of electrical energy.
It is overloadable by 10% in limited time peaks, maximum 1 every 12 hours. StandbyPower (LTP) “Emergency Service” is applicable for generator sets that operate when the Electrical Grid fails.
This power is NOT OVERCHARGED. However, to achieve a long engine life, it is recommended that the average active power load (kW) connected to the generating set in any 24-hour period of operation should not be higher than the following values:
• In Main Service, at 70% of the PRP power.
• In Emergency Service due to network failure, at 80% of the LTP power